Germany VDE-AR-N 4110 (Medium Voltage)

This section describes the parameter configuration for the ABB CM-UFD.M31 and CM-UFD.M31M relays to comply with the VDE-AR-N 4110 standard in Germany.

This standard governs grid connection requirements for systems connected to the medium-voltage network and defines precise thresholds for voltage, frequency, and fault detection to ensure system stability and safety within the public grid infrastructure.

Germany VDE-AR-N 4110 settings for ABB CM-UFD.M31(M)

Menu

Submenu

 

Configuration option

Monitoring functions

Overvoltage >UAV

Monitoring

disabled

Monitoring functions

Overvoltage >UAV

Threshold value

0.005 xUn

Monitoring functions

Overvoltage >UAV

Hysteresis

0.1 %

Monitoring functions

Overvoltage >U1

Monitoring

enabled

Monitoring functions

Overvoltage >U1

Threshold value

1.25 x Un

Monitoring functions

Overvoltage >U1

Hysteresis

1 %

Monitoring functions

Overvoltage >U1

Tripping delay

0.1 s

Monitoring functions

Overvoltage >U2

Monitoring

disabled

Monitoring functions

Overvoltage >U2

Threshold value

0.005 x Un

Monitoring functions

Overvoltage >U2

Hysteresis

0.1 %

Monitoring functions

Overvoltage >U2

Tripping delay

0.01 s

Monitoring functions

Undervoltage <U1

Monitoring

enabled

Monitoring functions

Undervoltage <U1

Threshold value

0.8 x Un

Monitoring functions

Undervoltage <U1

Hysteresis

1 %

Monitoring functions

Undervoltage <U1

Tripping delay

2.4 s

Monitoring functions

Undervoltage <U2

Monitoring

enabled

Monitoring functions

Undervoltage <U2

Threshold value

0.3 x Un

Monitoring functions

Undervoltage <U2

Hysteresis

1 %

Monitoring functions

Undervoltage <U2

Tripping delay

0.8 s

Monitoring functions

Overfrequency >F1

Monitoring

enabled

Monitoring functions

Overfrequency >F1

Threshold value

51.5 Hz

Monitoring functions

Overfrequency >F1

Hysteresis

0.1 Hz

Monitoring functions

Overfrequency >F1

Tripping delay

5 s

Monitoring functions

Overfrequency >F2

Monitoring

enabled

Monitoring functions

Overfrequency >F2

Threshold value

52.5 Hz

Monitoring functions

Overfrequency >F2

Hysteresis

0.1 Hz

Monitoring functions

Overfrequency >F2

Tripping delay

0.1 s

Monitoring functions

Underfrequency <F1

Monitoring

enabled

Monitoring functions

Underfrequency <F1

Threshold value

47.5 Hz

Monitoring functions

Underfrequency <F1

Hysteresis

0.1 Hz

Monitoring functions

Underfrequency <F1

Tripping delay

0.1 s

Monitoring functions

Underfrequency <F2

Monitoring

disabled

Monitoring functions

Underfrequency <F2

Threshold value

0.01 Hz

Monitoring functions

Underfrequency <F2

Hysteresis

0.01 Hz

Monitoring functions

Underfrequency <F2

Tripping delay

0.01 s

Monitoring functions

ROCOFClosed Short for "Rate of Change of Frequency". In grid monitoring relays, it refers to how quickly the electrical frequency is changing over time. It's used to detect unstable grid conditions - especially during events like load shedding or generator disconnection - and can trigger protective actions if the frequency changes too rapidly.

Monitoring

disabled

Monitoring functions

ROCOF

Threshold value

0.005 Hz/s

Monitoring functions

ROCOF

Number of cycles

1

Monitoring functions

ROCOF

Tripping delay

0.01 s

Monitoring functions

ROCOF

Error time

0.01 s

Monitoring functions

Vector Shift VS

Monitoring

disabled

Monitoring functions

Vector Shift VS

Threshold value

0.1*

Monitoring functions

Vector Shift VS

Error time

0.01 s

Switch-on conditions

Switch-on delay

Switch-on delay

600 s

Switch-on conditions

Switch-on delay

Short interruption

enabled

Switch-on conditions

Voltage window

Monitoring

enabled

Switch-on conditions

Voltage window

Minimum

49.9 Hz

Switch-on conditions

Voltage window

Maximum

50.1 Hz

Switch-on conditions

Frequency window

Monitoring

enabled

Switch-on conditions

Frequency window

Minimum

49.8

Switch-on conditions

Frequency window

Maximum

50.2