Germany VDE-AR-N 4110 (Medium Voltage)
This section describes the parameter configuration for the ABB CM-UFD.M31 and CM-UFD.M31M relays to comply with the VDE-AR-N 4110 standard in Germany.
This standard governs grid connection requirements for systems connected to the medium-voltage network and defines precise thresholds for voltage, frequency, and fault detection to ensure system stability and safety within the public grid infrastructure.
Menu |
Submenu |
Configuration option |
|
---|---|---|---|
Monitoring functions |
Overvoltage >UAV |
Monitoring |
disabled |
Monitoring functions |
Overvoltage >UAV |
Threshold value |
0.005 xUn |
Monitoring functions |
Overvoltage >UAV |
Hysteresis |
0.1 % |
Monitoring functions |
Overvoltage >U1 |
Monitoring |
enabled |
Monitoring functions |
Overvoltage >U1 |
Threshold value |
1.25 x Un |
Monitoring functions |
Overvoltage >U1 |
Hysteresis |
1 % |
Monitoring functions |
Overvoltage >U1 |
Tripping delay |
0.1 s |
Monitoring functions |
Overvoltage >U2 |
Monitoring |
disabled |
Monitoring functions |
Overvoltage >U2 |
Threshold value |
0.005 x Un |
Monitoring functions |
Overvoltage >U2 |
Hysteresis |
0.1 % |
Monitoring functions |
Overvoltage >U2 |
Tripping delay |
0.01 s |
Monitoring functions |
Undervoltage <U1 |
Monitoring |
enabled |
Monitoring functions |
Undervoltage <U1 |
Threshold value |
0.8 x Un |
Monitoring functions |
Undervoltage <U1 |
Hysteresis |
1 % |
Monitoring functions |
Undervoltage <U1 |
Tripping delay |
2.4 s |
Monitoring functions |
Undervoltage <U2 |
Monitoring |
enabled |
Monitoring functions |
Undervoltage <U2 |
Threshold value |
0.3 x Un |
Monitoring functions |
Undervoltage <U2 |
Hysteresis |
1 % |
Monitoring functions |
Undervoltage <U2 |
Tripping delay |
0.8 s |
Monitoring functions |
Overfrequency >F1 |
Monitoring |
enabled |
Monitoring functions |
Overfrequency >F1 |
Threshold value |
51.5 Hz |
Monitoring functions |
Overfrequency >F1 |
Hysteresis |
0.1 Hz |
Monitoring functions |
Overfrequency >F1 |
Tripping delay |
5 s |
Monitoring functions |
Overfrequency >F2 |
Monitoring |
enabled |
Monitoring functions |
Overfrequency >F2 |
Threshold value |
52.5 Hz |
Monitoring functions |
Overfrequency >F2 |
Hysteresis |
0.1 Hz |
Monitoring functions |
Overfrequency >F2 |
Tripping delay |
0.1 s |
Monitoring functions |
Underfrequency <F1 |
Monitoring |
enabled |
Monitoring functions |
Underfrequency <F1 |
Threshold value |
47.5 Hz |
Monitoring functions |
Underfrequency <F1 |
Hysteresis |
0.1 Hz |
Monitoring functions |
Underfrequency <F1 |
Tripping delay |
0.1 s |
Monitoring functions |
Underfrequency <F2 |
Monitoring |
disabled |
Monitoring functions |
Underfrequency <F2 |
Threshold value |
0.01 Hz |
Monitoring functions |
Underfrequency <F2 |
Hysteresis |
0.01 Hz |
Monitoring functions |
Underfrequency <F2 |
Tripping delay |
0.01 s |
Monitoring functions |
Monitoring |
disabled |
|
Monitoring functions |
ROCOF |
Threshold value |
0.005 Hz/s |
Monitoring functions |
ROCOF |
Number of cycles |
1 |
Monitoring functions |
ROCOF |
Tripping delay |
0.01 s |
Monitoring functions |
ROCOF |
Error time |
0.01 s |
Monitoring functions |
Vector Shift VS |
Monitoring |
disabled |
Monitoring functions |
Vector Shift VS |
Threshold value |
0.1* |
Monitoring functions |
Vector Shift VS |
Error time |
0.01 s |
Switch-on conditions |
Switch-on delay |
Switch-on delay |
600 s |
Switch-on conditions |
Switch-on delay |
Short interruption |
enabled |
Switch-on conditions |
Voltage window |
Monitoring |
enabled |
Switch-on conditions |
Voltage window |
Minimum |
49.9 Hz |
Switch-on conditions |
Voltage window |
Maximum |
50.1 Hz |
Switch-on conditions |
Frequency window |
Monitoring |
enabled |
Switch-on conditions |
Frequency window |
Minimum |
49.8 |
Switch-on conditions |
Frequency window |
Maximum |
50.2 |