General settings for ABB CM-UFD.M31(M)
Log into the menu of the ABB CM-UFD.M31(M) device and make the settings described in this section.
Note:
- The default password is 0000.
- Remember to save any setting you specify or change.
Menu |
Submenu |
Configuration option |
|
---|---|---|---|
Nominal voltage |
Measuring principle |
3L-N + 3L-L |
|
Nominal voltage |
Nominal voltage |
230 V L-N 400 V L-L |
|
I/O setup |
Relay R3 |
Working principle |
sync. with R1/R2 |
I/O setup |
Relay R3 |
ON-delay |
0 s |
I/O setup |
Relay R3 |
ON-time |
0.5 s |
I/O setup |
Feedback Y1 |
Monitoring |
disabled |
I/O setup |
Feedback Y1 |
Trip window |
0.01 s |
I/O setup |
Feedback Y1 |
Release window |
0.1 s |
I/O setup |
Feedback Y2 |
Monitoring |
disabled |
I/O setup |
Feedback Y2 |
Trip window |
0.01 s |
I/O setup |
Feedback Y2 |
Release window |
0.1 s |
I/O setup |
Control Input Y3 |
Function |
disabled |
I/O setup |
Auto reconnection |
Number of attempts |
0 |
General settings |
Language |
Language |
English |
General settings |
Display |
Switch-off delay |
Leave the default value 10 s |
General settings |
Display |
Contrast |
Leave the default value 5 s |
General settings |
Plant Operator Password |
Protection |
enabled |
General settings |
Plant Operator Password |
Change password |
[****] Note: XOLTA recommends changing the default password for security reasons. |
General settings |
Grid Operator Password |
Protection |
enabled |
General settings |
Grid Operator Password |
Change password |
[****] Note: XOLTA recommends changing the default password for security reasons. |
General settings |
Load settings |
"Setting name" |
Important: Remember to save. Otherwise, the value is overwritten after device power cycling. |
General settings |
Save settings |
"Setting name" |
Important: Remember to save. Otherwise, the value is overwritten after device power cycling. |
Modbus |
Bus mode |
Communication |
disabled |
Modbus |
Bus mode |
Remote trip via bus |
disabled or enabled |
Modbus |
Bus mode |
Fault reaction |
trip R1/R2 or fault message |
Modbus |
Bus mode |
Timeout |
1 s |
Modbus |
Bus configuration |
Slave address |
1 |
Error memory |
Error recording |
Remote trip via Y3 |
Leave the default value |
Error memory |
Error recording |
Remote trip via bus |
Leave the default value |
Error memory |
Error recording |
Power OFF |
Leave the default value |