General settings for ABB CM-UFD.M31(M)

Log into the menu of the ABB CM-UFD.M31(M) device and make the settings described in this section.

Note

  • The default password is 0000.
  • Remember to save any setting you specify or change.
General settings for ABB CM-UFD.M31(M)

Menu

Submenu

Configuration option

Nominal voltage

Measuring principle

 

3L-N + 3L-L

Nominal voltage

Nominal voltage

 

230 V L-N

400 V L-L

I/O setup

Relay R3

Working principle

sync. with R1/R2

I/O setup

Relay R3

ON-delay

0 s

I/O setup

Relay R3

ON-time

0.5 s

I/O setup

Feedback Y1

Monitoring

disabled

I/O setup

Feedback Y1

Trip window

0.01 s

I/O setup

Feedback Y1

Release window

0.1 s

I/O setup

Feedback Y2

Monitoring

disabled

I/O setup

Feedback Y2

Trip window

0.01 s

I/O setup

Feedback Y2

Release window

0.1 s

I/O setup

Control Input Y3

Function

disabled

I/O setup

Auto reconnection

Number of attempts

0

General settings

Language

Language

English

General settings

Display

Switch-off delay

Leave the default value 10 s

General settings

Display

Contrast

Leave the default value 5 s

General settings

Plant Operator Password

Protection

enabled

General settings

Plant Operator Password

Change password

[****]

NoteXOLTA recommends changing the default password for security reasons.

General settings

Grid Operator Password

Protection

enabled

General settings

Grid Operator Password

Change password

[****]

NoteXOLTA recommends changing the default password for security reasons.

General settings

Load settings

"Setting name"

Important

Remember to save. Otherwise, the value is overwritten after device power cycling.

General settings

Save settings

"Setting name"

Important

Remember to save. Otherwise, the value is overwritten after device power cycling.

Modbus

Bus mode

Communication

disabled

Modbus

Bus mode

Remote trip via bus

disabled

or

enabled

Modbus

Bus mode

Fault reaction

trip R1/R2

or

fault message

Modbus

Bus mode

Timeout

1 s

Modbus

Bus configuration

Slave address

1

Error memory

Error recording

Remote trip via Y3

Leave the default value

Error memory

Error recording

Remote trip via bus

Leave the default value

Error memory

Error recording

Power OFF

Leave the default value