Germany – VDE-AR-N 4105 (Low Voltage)

This section outlines the country-specific parameter settings for the ABB CM-UFD.M31 and CM-UFD.M31M grid monitoring relays, as required for compliance with the German VDE-AR-N 4105 standard for low-voltage grid connections.

These settings ensure proper integration of distributed energy resources into the public grid by adhering to the national limits for voltage, frequency, and disconnection behavior, as defined for systems connected to the low-voltage distribution network.

Germany VDE-AR-N 4105 settings for ABB CM-UFD.M31(M)

Menu

Submenu

 

Configuration option

Monitoring functions

Overvoltage >UAV

Monitoring

enabled

Monitoring functions

Overvoltage >UAV

Threshold value

1.1 x Un

Monitoring functions

Overvoltage >UAV

Hysteresis

0.1 %

Monitoring functions

Overvoltage >U1

Monitoring

enabled

Monitoring functions

Overvoltage >U1

Threshold value

1.25 x Un

Monitoring functions

Overvoltage >U1

Hysteresis

1 %

Monitoring functions

Overvoltage >U1

Tripping delay

0.1 s

Monitoring functions

Overvoltage >U2

Monitoring

disabled

Monitoring functions

Overvoltage >U2

Threshold value

0.005 x Un

Monitoring functions

Overvoltage >U2

Hysteresis

0.1 %

Monitoring functions

Overvoltage >U2

Tripping delay

0.01 s

Monitoring functions

Undervoltage <U1

Monitoring

enabled

Monitoring functions

Undervoltage <U1

Threshold value

0.8 x Un

Monitoring functions

Undervoltage <U1

Hysteresis

1 %

Monitoring functions

Undervoltage <U1

Tripping delay

1 s

Monitoring functions

Undervoltage <U2

Monitoring

enabled

Monitoring functions

Undervoltage <U2

Threshold value

0.45 x Un

Monitoring functions

Undervoltage <U2

Hysteresis

1 %

Monitoring functions

Undervoltage <U2

Tripping delay

0.3 s

Monitoring functions

Overfrequency >F1

Monitoring

enabled

Monitoring functions

Overfrequency >F1

Threshold value

51.5 Hz

Monitoring functions

Overfrequency >F1

Hysteresis

0.1 Hz

Monitoring functions

Overfrequency >F1

Tripping delay

0.1 s

Monitoring functions

Overfrequency >F2

Monitoring

disabled

Monitoring functions

Overfrequency >F2

Threshold value

0.01 Hz

Monitoring functions

Overfrequency >F2

Hysteresis

0.01 Hz

Monitoring functions

Overfrequency >F2

Tripping delay

0.01 s

Monitoring functions

Underfrequency <F1

Monitoring

enabled

Monitoring functions

Underfrequency <F1

Threshold value

47.5 Hz

Monitoring functions

Underfrequency <F1

Hysteresis

0.1 Hz

Monitoring functions

Underfrequency <F1

Tripping delay

0.1 s

Monitoring functions

Underfrequency <F2

Monitoring

disabled

Monitoring functions

Underfrequency <F2

Threshold value

0.01 Hz

Monitoring functions

Underfrequency <F2

Hysteresis

0.01 Hz

Monitoring functions

Underfrequency <F2

Tripping delay

0.01 s

Monitoring functions

ROCOFClosed Short for "Rate of Change of Frequency". In grid monitoring relays, it refers to how quickly the electrical frequency is changing over time. It's used to detect unstable grid conditions - especially during events like load shedding or generator disconnection - and can trigger protective actions if the frequency changes too rapidly.

Monitoring

disabled

Monitoring functions

ROCOF

Threshold value

0.005 Hz/s

Monitoring functions

ROCOF

Number of cycles

1

Monitoring functions

ROCOF

Tripping delay

0.01 s

Monitoring functions

ROCOF

Error time

0.01 s

Monitoring functions

Vector Shift VS

Monitoring

disabled

Monitoring functions

Vector Shift VS

Threshold value

0.1*

Monitoring functions

Vector Shift VS

Error time

0.01 s

Switch-on conditions

Switch-on delay

Switch-on delay

60 s

Switch-on conditions

Switch-on delay

Short interruption

enabled

Switch-on conditions

Voltage window

Monitoring

enabled

Switch-on conditions

Voltage window

Minimum

0.85 x Un

Switch-on conditions

Voltage window

Maximum

1.1 x Un

Switch-on conditions

Frequency window

Monitoring

enabled

Switch-on conditions

Frequency window

Minimum

47.5

Switch-on conditions

Frequency window

Maximum

50.1